HVLS Fans for Warehouses

A warehouse is the clearest case for HVLS fans in Canada, because the building works against you in both seasons. In summer, stagnant air at floor level makes picking areas uncomfortable long before the thermometer justifies it. In winter, the heat you paid for collects at the ceiling where nobody works.

Why warehouse air stratifies so badly

Warm air rises, and in a building with 24 ft or more of clear height there is nothing to bring it back down. A published field study of a 100,000 sq ft warehouse in Brampton measured ceiling temperatures dropping about 4.0°C and floor temperatures rising about 1.5°C once destratification fans were running -- the same heat, redistributed to where people work.

That study measured roughly a 20% reduction in natural gas use across the heating season, with the fans paying for themselves in under five years.

How many fans a warehouse needs

Fan count comes from floor area, ceiling height and how much of the floor plate is open. A 20 ft fan has a de-stratifying influence of roughly 7,850 sq ft. The Brampton study covered 100,000 sq ft with five of them.

Racking changes the answer. A building packed with 20 ft racking moves far less air per fan than an open staging floor, so the estimator applies an obstruction factor rather than dividing area by coverage and stopping there.

Clear height Typical fan diameter Approximate coverage per fan
16–19 ft 16 ft 5,156 sq ft
20–21 ft 20 ft 8,056 sq ft
22–24 ft 24 ft 11,600 sq ft
25 ft+ 24 ft 11,600 sq ft

Coverage figures are the denominators Enbridge Gas publishes for its own incentive eligibility calculation.

Where fans go, and where they can't

Fans need to hang in open volume. The usable positions in most warehouses are the staging and shipping area, the cross-aisle, the pick-module face, and any bay left open for turning room.

What rules a position out: sprinkler heads and their clearance requirements, overhead cranes, conveyor runs, and mezzanine decks that cut the column of air the fan needs.

Heating type decides whether you save money

Destratification only pays back where there is warm air at the ceiling to bring down. Gas unit heaters and rooftop units mounted at roof level create exactly that.

Radiant tube heaters do not. They heat surfaces and people directly rather than the air, so there is far less stratification to recover -- and Enbridge's incentive excludes buildings with radiant or high-velocity vertical-throw heaters in the fan's influence area.

Size Your HVLS Fan Package In 30 Seconds

Tell us about your facility

Frequently asked questions

Will an HVLS fan actually cool the building?

No. It moves air, it doesn't refrigerate it. What it produces is an evaporative cooling effect on skin -- a perceived drop of several degrees for people standing in the airflow, with no change in measured air temperature.

Can we run them in winter?

That's where most of the money is. Run slowly and often in reverse, they push ceiling heat back down without creating a draft at floor level.

How much do they cost?

An HVLS fan unit starts at $7,000 for an 8 ft fan and $7,500 at 16 ft. Drives, mounts, controls, freight and installation are quoted separately. The estimator gives supply-only figures.

Do they interfere with sprinklers?

This has to be reviewed for your building rather than answered generally. Raise it with your sprinkler contractor before finalising fan positions.

Are there rebates?

Enbridge Gas offers a prescriptive incentive for destratification fans in warehousing-type buildings with 22 ft or higher ceilings and gas forced-air heating, subject to several eligibility conditions. The rebate estimator checks yours.