HVLS Fan Sizing

Sizing comes down to three inputs: how much floor you have, how high the ceiling is, and how much of the volume is actually open.

Coverage per diameter

These are the coverage denominators Enbridge Gas publishes for its destratification incentive eligibility calculation, which makes them the most defensible public figures available.

Diameter Coverage per fan
12 ft 2,900 sq ft
14 ft 3,947 sq ft
16 ft 5,156 sq ft
18 ft 6,525 sq ft
20 ft 8,056 sq ft
22 ft 9,748 sq ft
24 ft 11,600 sq ft

Coverage rises faster than diameter -- a 24 ft fan covers four times a 12 ft fan, not twice.

Ceiling height sets the diameter

A large fan needs height to develop its column before it reaches the floor, and it needs clearance above people and equipment.

Clear height Typical diameter
Under 16 ft 8–12 ft
16–19 ft 16 ft
20–21 ft 20 ft
22–24 ft 24 ft
25 ft and above 24 ft

Obstructions change everything

Coverage figures assume open volume. Real buildings aren't.

Racking, mezzanines, cranes and conveyors all cut the air's path. A building full of 20 ft racking delivers far less per fan than an open floor of the same area, which is why a sizing estimate that asks only for square footage isn't one.

Fewer large fans or more small ones?

Larger fans cover more per unit and cost less per square foot covered. Smaller fans fit around obstructions and suit lower ceilings. Most buildings end up with the largest diameter the ceiling and the obstructions will allow.

Sprinkler requirements can override this entirely -- see the sprinkler guide.

Size Your HVLS Fan Package In 30 Seconds

Tell us about your facility

Frequently asked questions

How many fans for 100,000 sq ft?

In an open building with a high ceiling, single digits. The Brampton field study covered 100,000 sq ft with five 20 ft fans.

Can I put one big fan in the middle?

Only if the area is within one fan's coverage. Beyond that the far corners get nothing.

Does fan count change my rebate?

Yes. Enbridge caps eligible fans using floor area and the coverage figures above, so installing more than the formula allows doesn't increase the incentive.

What if my ceiling is under 16 ft?

HVLS still works but coverage per fan drops steeply, and the economics get harder to justify.