Destratification Explained
Warm air rises. In a building with a 30 ft ceiling that means the heat you paid for spends the winter at roof level, above everyone.
What stratification looks like in numbers
The gradient in a tall heated building can be several degrees between floor and ceiling. A published field study of a 100,000 sq ft warehouse in Brampton measured ceiling temperatures falling about 4.0°C and floor temperatures rising about 1.5°C once destratification fans ran -- the difference being heat that had been stacked at the roof.
The same study measured roughly 20% less natural gas across the heating season, with payback under five years.
Why it costs money twice
Stratification charges you twice over. The thermostat is at floor level, so it keeps calling for heat while the ceiling is already warm. And the hotter the roof deck, the more heat escapes through it -- heat loss rises with the temperature difference across the assembly.
Destratification addresses both at once: the occupied zone gets warmer without more gas, and the roof plane gets cooler so it loses less.
Where it works, and where it doesn't
| Condition | Destratification case |
|---|---|
| Gas unit heaters or rooftop units at roof level | Strong. This is the case the savings were measured in |
| Ceiling 22 ft or higher | Strong. More gradient to recover |
| Ceiling under 20 ft | Weaker. Less gradient exists |
| Radiant tube or infrared heating | Weak. Heats surfaces, not air, so little gradient forms |
| Unheated building | None. Nothing at the ceiling to recover |
Enbridge's incentive excludes buildings with radiant or high-velocity vertical-throw heaters in the fan's influence area, for exactly this reason.
Estimate Your Energy Savings In 30 Seconds
Tell us about your facility
Frequently asked questions
Do I run the fan in reverse in winter?
Direction and speed are both settings. What matters is that winter operation is slow -- enough to mix, not enough to create a draft people feel.
How much can I actually save?
The one well-documented Canadian figure is around 20% of heating gas in a tall warehouse with gas forced-air heating. Your building's gradient, heating type and hours all change that.
Will it make the floor too warm?
No. It redistributes heat that already exists. The floor rises by a degree or two.
Does it help in summer?
Different mechanism. Summer benefit is perceived cooling from air movement, not destratification.